AMC16-DETT telecommunication tower DC Power Meter
● DC rated voltage: 1 channel: -48VDC
● Accuracy:1%In≤I≤10%In error±2.5%; I>10%In error±2%
● RS485(MODBUS-RTU)
● LED display
● DIN 35 mm

PRODUCTS

  • General

    Base station dedicated DC energy meter AMC16-DETT is specially designed for base stations where have sharing requirements, and switch power supply is without the function of sub-user metering.

    The meter could measure6 circuits DC energy, and supply working current to the matched hall sensors. Meanwhile, it can realize zero drift calibration by upper computer software.have the functions of telemetering,teleindication,teleadjusting, metering at real time,energy quality abnormal alarm, data storage and processing, data interaction.


    Functions

                                         

    IMG_7811.jpg

    Communication

    Single channel RS485 communication protocol

    Standard or customized



    Rated U and I

    Total 200A/5V



    Accuracy

    1%In≤I≤10%In error±2.5%;I>10%In error±2%



    Voltage range

    -40V~-60VDC



    Power consumption

    ≤2W( no hall power supply output)

    Power supply output

    +12V/100Ma, -12V/50mA



    Power consumption

    ≤2W( no hall power supply output)



    Dimension(L*W*H)

    89.7*87.8*52mm



    Installation

    DIN 35 mm



    Clock

    ≤0.5S/d(23℃), ≤1S/d(-20℃-60℃)



    Current

    1.2 times continued

    IMG_7814.jpg


    Wiring

    1.jpg




    ① Digital input


    ② Brand/Model


    ③ Panel


    ④ Digital output


    ⑤ Pluse output

    2.jpg


    Dimension

    3.jpg


    Network

    4.jpg

    Installation On Site

    5.png6.png

  • Technical Parameters

    Technical parameter

    Index

    Input

    DC rated voltage

    1 channel: -48VDC

    DC current

    6 channels hall sensors: total 200A/5V, China Telecom, China
    Mobile, China Unicom and the 1st channel reserve 50A/5V, 2nd
    channel reserve 100A/5V

    Commercial power
    monitoring

    1 channel: 0-5VDC

    Overload capacity

    Voltage:1.2times continued,2 times continued 1s;
    Current: 1.2 times continued,10 times continued 1s

    Accuracy (superposition hall sensors)

    1%In≤I≤10%In error±2.5%; I>10%In error±2%

    Measurement resolution

    Voltage output accuracy 0.01V; current output accuracy 0.01A;
    power output accuracy 0.01kw; energy output accuracy 0.01kwh

    Functions

    Basic function

    Monitor device system time, total voltage, output total current, power, energy, each channel voltage, current, power, energy; LED indicator display;485 communication.

    Metering function

    Start current: under rated voltage, when the load current value of the meter doesn’t exceed 1% of the max. current, the meter starts.
    Shunt running current: when there is no current in the current
    circuit of the meter, and 85%-125%of the rated voltage is applied on the voltage circuit, the calculator shall not have more than one digital change.

    Alarm function

    DC voltage output low alarm,DC voltage output high alarm,one
    power down alarm, module voltage loss alarm, metering branch
    error alarm, internal program error alarm, clock error alarm,
    memory failure alarm, AC input power failure alarm

    Timing function

    support broadcast timing, could remote timing to the meter
    through RS485 communication.

    Communication

    Single channel RS485, baudrate 9600bps, can be set to 1200BPS,
    2400bps, 4800bps.
    Communication protocol: standard or custmized

    Hall sensor power supply

    Power supply output:+12V/100Ma, -12V/50mA

    Clock accuracy

    ≤0.5S/d(23℃), ≤1S/d(-20℃-60℃),

    Auxiliary
    supply

    Voltage range

    -40V~-60VDC

    Power consumption

    Whole device≤2W( no hall power supply output)

    Storage

    It has the storage function of historical power data and historical alarm information, and the memory is 2MB

    Insulation resistance

    ≥40MΩ

    Environment

    Temperature

    Working : -20℃~+60℃; storage:-40℃~+70℃

    Humidity

    ≤98% no condensation, no corrosive gas place

    Altitude

    ≤4000m

    Protection level

    IP20

    Material flame retardent

    Terminal glow wire temperature 960℃±10℃ ,shell glow wire
    temperature 6500℃±15℃

    Installation

    Standard 35mm din rail

    Lightning
    protection

    Voltage input
    (differential mode)

    Peak value 5kA

    Auxiliary supply
    (differential mode)

    Peak value 5kA


  • 20200812132634270.png@!w1600