Base station dedicated DC energy meter AMC16-DETT is specially designed for base stations where have sharing requirements, and switch power supply is without the function of sub-user metering.
The meter could measure6 circuits DC energy, and supply working current to the matched hall sensors. Meanwhile, it can realize zero drift calibration by upper computer software.have the functions of telemetering,teleindication,teleadjusting, metering at real time,energy quality abnormal alarm, data storage and processing, data interaction.
Communication Single channel RS485 communication protocol Standard or customized Rated U and I Total 200A/5V Accuracy 1%In≤I≤10%In error±2.5%;I>10%In error±2% Voltage range -40V~-60VDC Power consumption ≤2W( no hall power supply output) | |
Power supply output +12V/100Ma, -12V/50mA Power consumption ≤2W( no hall power supply output) Dimension(L*W*H) 89.7*87.8*52mm Installation DIN 35 mm Clock ≤0.5S/d(23℃), ≤1S/d(-20℃-60℃) Current 1.2 times continued |
① Digital input ② Brand/Model ③ Panel ④ Digital output ⑤ Pluse output |
Technical Parameters
Technical parameter | Index | |
Input | DC rated voltage | 1 channel: -48VDC |
DC current | 6 channels hall sensors: total 200A/5V, China Telecom, China | |
Commercial power | 1 channel: 0-5VDC | |
Overload capacity | Voltage:1.2times continued,2 times continued 1s; | |
Accuracy (superposition hall sensors) | 1%In≤I≤10%In error±2.5%; I>10%In error±2% | |
Measurement resolution | Voltage output accuracy 0.01V; current output accuracy 0.01A; | |
Functions | Basic function | Monitor device system time, total voltage, output total current, power, energy, each channel voltage, current, power, energy; LED indicator display;485 communication. |
Metering function | Start current: under rated voltage, when the load current value of the meter doesn’t exceed 1% of the max. current, the meter starts. | |
Alarm function | DC voltage output low alarm,DC voltage output high alarm,one | |
Timing function | support broadcast timing, could remote timing to the meter | |
Communication | Single channel RS485, baudrate 9600bps, can be set to 1200BPS, | |
Hall sensor power supply | Power supply output:+12V/100Ma, -12V/50mA | |
Clock accuracy | ≤0.5S/d(23℃), ≤1S/d(-20℃-60℃), | |
Auxiliary | Voltage range | -40V~-60VDC |
Power consumption | Whole device≤2W( no hall power supply output) | |
Storage | It has the storage function of historical power data and historical alarm information, and the memory is 2MB | |
Insulation resistance | ≥40MΩ | |
Environment | Temperature | Working : -20℃~+60℃; storage:-40℃~+70℃ |
Humidity | ≤98% no condensation, no corrosive gas place | |
Altitude | ≤4000m | |
Protection level | IP20 | |
Material flame retardent | Terminal glow wire temperature 960℃±10℃ ,shell glow wire | |
Installation | Standard 35mm din rail | |
Lightning | Voltage input | Peak value 5kA |
Auxiliary supply | Peak value 5kA |