ASD series switch cabinet integrated measuring and control device is used for 3-35kV indoor switch cabinet, applying to centrally installed switchgear, trolley cabinet, fixed switchgear, ring main unit and other various switch cabinets. With primary circuit mimetic diagram and switch status indicator, HV live displaying and nuclear phase, automatic temperature and humidity control, heating circuit fault alarm, wireless temperature measurement, body induction auto lighting, voice prompt, electrical parameter measurement and RS485 communication interface and other numerous functions, it has integrated operation and display into one. The product is classified into ASD100, ASD100G, ASD200, ASD300, ASD310, ASD320 six models according to its function.
function&type | ASD100/ASD100G | ASD200 | ASD300 | ASD310 | ASD320 | |
Product picture | ||||||
Cutout | 112mm×172mm | 220mm×165mm | ||||
Primary circuit analog chart | Standard | |||||
LIve display and self-test/nuclear phase | Optional,need to order instructions | |||||
Electromagnetic lockout outlet | Configuration 1 | Configuration 2 | Configuration 1 | |||
Temp./humidity control | Standard 1 sensor,line lengh 4meters | |||||
TWO heating One blowing | TWO heating | TWO heating One blowing | ||||
Forced heating | Standard | Standard | ||||
Heating circuit Fault alarm | Standard | None | ||||
Voice prompts | None | Standard | ||||
Sensing probe for humanbody | None | Standard | ||||
Operating knob | None | Optional | ||||
Beaker frequency shows | None | Standard | ||||
Wireless temperature measurement | None | None | Optional | None | Optional | |
Measure and display of power parameter | None | None | Standard | None | ||
Communication port | None | Standard |
Item | Value | ||||||
ASD100L | ASD100G | ASD200 | ASD300 | ASD310 | ASD320 | ||
Rated input | Wiring mode | —— | —— | —— | 3P3L or3P4L | —— | —— |
Voltage | —— | —— | —— | 100V | —— | —— | |
Current | —— | —— | —— | 5A | —— | —— | |
frequency | —— | —— | —— | 50Hz | —— | —— | |
Accuracy rating | Current、Voltage | —— | —— | —— | 0.5 class | —— | —— |
Active power | —— | —— | —— | 0.5class | —— | —— | |
Reactive power | —— | —— | —— | —— | —— | ||
Energy | —— | —— | —— | 0.5 class | |||
tripping circuit and closing circuit control voltage | —— | —— | 1 class | ||||
Environment temperature | —— | ±1℃ | |||||
Relative humidity | —— | ±5% | |||||
Device Working power | AC 85~265V,DC 100~300V | ||||||
Power consumption | Auxiliary power | ≤5VA | ≤5VA | ≤6VA | ≤8VA | ||
Voltage input | —— | —— | —— | ≤0.5VA | —— | —— | |
Current input | —— | —— | —— | ≤1VA | —— | —— | |
Communication | protocol | —— | MODBUS-RTU | ||||
Baud rate(bps) | —— | 2400、4800、9600、19200 | |||||
Wireless temperature measurement | Temperature measurement range | —— | —— | -50℃~+125℃ | —— | -50℃~+125℃ | |
Temperature measurement accuracy | —— | —— | ±1℃ | —— | ±1℃ | ||
Sensor battery life | —— | —— | ≥5 year | —— | ≥5 year | ||
starting current | —— | —— | ≥5A | —— | ≥5A | ||
Environmentalrequirement | Operating temperature | -10℃~55℃ | |||||
Relative humidity | ≤95% | ||||||
Average work time without stoppage | ≥50000 hour | —— | —— | —— | —— | —— |