ASJ10-GQ series self compound over and under voltage protector (referred to as ASJ) is suitable for single-phase AC voltage 230V or three-phase voltage 400V, frequency 45-65Hz,Users or loads with rated working current up to and including 63A. When the single-phase or three-phase line over-voltage or under voltage is caused by the neutral line fault, the protective device is opposite to the electrical equipment Protection.
ASJ series products have the functions of over-voltage, under voltage protection and automatic delay reset of line normal voltage. The products are mainly used in the residential box The protection of incoming line or single-phase or three-phase electrical equipment distribution line, with small volume, high precision, compact structure and convenient installation, is the safety in the field of civil construction Full protection device.
2 product features
■ auxiliary power supply AC230V (phase voltage).
■ cut off the line in case of over-voltage and under voltage, reset the line automatically after the line voltage returns to normal, and connect the line without manual operation.
■ voltage measurement range: ac50v-290v, frequency 50Hz ± 5Hz, product power consumption is not more than 3W.
■ impulse withstand voltage: 4KV.
■ the working state is indicated by the two-color diode of the protector, the green light is normally on - the voltage is normal; the red light is fast flashing - over-voltage; the red light is slow flashing - under voltage; the red light is normally on-Open phase / fault.
■ output capacity of relay: it can withstand the over-current of 120% current level of shell frame.
■ wiring mode: up in down out.
■ electrical life: 10000 times.
■ the product is installed on the outgoing side of the main switch of the household box.
3 model description
Current shell frame In | phase:1P | phase:3P |
25A | ASJ10-GQ-1P-25 | ASJ10-GQ-3P-25 |
32A | ASJ10-GQ-1P-32 | ASJ10-GQ-3P-32 |
40A | ASJ10-GQ-1P-40 | ASJ10-GQ-3P-40 |
50A | ASJ10-GQ-1P-50 | ASJ10-GQ-3P-50 |
63A | ASJ10-GQ-1P-63 | ASJ10-GQ-3P-63 |
4 main parameters
working voltage | 1P | AC230V 50Hz | ||||
3P | AC400V 50Hz | |||||
working frequency | 50Hz | |||||
Overvoltage trip (L-N) | 275VAC±5V | |||||
Overvoltage trip time | Overvoltage action setting value | 250V | 275V | 300V | 350V | 400V |
Maximum action time | no action | 15s | 3s | 0.75s | 0.2s | |
Default action time | 5s | 2s | 0.5s | 0.15s | ||
Minimum non driving time | 3s | 1s | 0.25s | 0.1s | ||
Overvoltage recovery (L-N) | 255VAC±5V | |||||
Undervoltage trip (L-N) | 160VAC±5V | |||||
Undervoltage trip time | 1s | |||||
Undervoltage recovery (L-N) | 195VAC±5V | |||||
Self recovery forced delay | 30s | |||||
Wiring mode | Up in down out | |||||
Electrical life | 10000 times | |||||
Protection level | noumenon | IP20 | ||||
Environment | Working environment temperature | _5℃~+40℃ | ||||
Storage ambient temperature | _20℃~+60℃ | |||||
humidity | ≤95% | |||||
altitude | ≤2000m | |||||
Pollution level | Level 2 |