AMC72L-E4/KC Three Phase AC Multi Function Panel Energy Meter
● Measurement: 3-phase AC kWh, kVarh, I, U, kW, kVar, Hz, cosφ and etc
● Accuracy: 1% (kWh); 0.5% (Active Power)
● Rated Voltage: 400V AC L-L (direct connect); 100V AC L-L (via PTs)
● Rated Current: 5A AC or 1A AC (via CTs)
● Power Supply: 85~265V AC/DC; 24V or 48V DC
● Communication: RS485 (MODBUS-RTU)
● SOE Funciton: Event&Demand&Extremum Record
● Harmonic Measurement: 2~31st and total Harmonic
● Analog Output: 4~20mA DC or 1~5V DC
● DI/DO Function: 2/4-channel DI&2-channel DO
● Standard&Certificate: CE Certificates

PRODUCTS

  • Products Overview

    Main Functions

    1.jpg


    Panel Overview

    2.jpg

    Main Parameters

    3.jpg


    Dimension

    Outline Dimension

    4.jpg


    Cut-out Dimension

    5.jpg



    Wiring Illustration

    6.jpg

    AC Voltage Signal (400V AC L-L) Input via direct Connection & AC Current Signal (5A or 1A AC) input via -/5A AC or -/1A AC CTs (3-phase 4-wire)

    7.jpg

    AC Voltage Signal (400V AC L-L) Input via direct Connection & AC Current Signal (5A or 1A AC) input via -/5A AC or -/1A AC CTs (3-phase 3-wire)

    8.jpg


    AC Voltage Signal (100V AC L-L) Input via -/100V AC PTs & AC Current Signal (5A or 1A AC) input via -/5A AC or -/1A AC CTs (3-phase 4-wire)


    9.jpg

    AC Voltage Signal (100V AC L-L) Input via -/100V AC PTs & AC Current Signal (5A or 1A AC) input via -/5A AC or -/1A AC CTs (3-phase 3-wire)


    Installation Instruction

    7.jpg

    1. Cut out a hole on the object on where we will intall the meter according to dimension of meter referred above.

    2. Remove the buckle on the meter off.

    8.jpg

    3. Install the meter into the cut-out hole.

    4. Buckle up and fixed the meter.


  • 1.Function Overview

    FunctionDescription&Value
    Measurement

    Three-phase AC kWh, kVarh, Active Power, Reactive Power, Forward&Reverse Power, Current, Voltage, Zero Sequence Voltage, Zero sequence Current, Voltage-phase Angle, Voltage&Current Unbalance, Power Factor,Harmonic, Frequency

    Display

    LCD display

    Communication(Optional)

    RS485,Modbus-RTU protocol;(1 start bit,8 data bit,1 stop bit,no parity)

    Baud Rate 1200~38400 bps etc.

    Alarm Output(Optional)

    1 channel passive relay,contact capacity 3A/30VDC,3A/250VAC,

    Used for high,low,unbalance alarm etc.

    Analog Output(Optional)

    1~5V DC or 4~20mA DC

    DI/DO Switching(Optional)

    DI (Digital input): 2-channel or 4-channel dry contact digital input with built in power supply

    DO (Digital output): 2-channel digital output with NO relay contact. Capacity: 3A/30V DC,3A/250V AC


    2. Main Parameters

    ParameterDescription&Value
    InputRated VoltageAC Voltage Input: 400V AC L-L (via direct connetion); 100V AC L-L (via -/100V AC PTs)
    Rated Current AC Current Input: 5A AC or 1A AC (via -/5A AC or -/1A AC CTs)
    Overload

    Current&Voltage input overload:1.2 times rated value(continuous); 10 times rated value /1 second

    Frequency45~65Hz
    Power Consumption

    Power consumption of each current&voltage input circuit is less than 0.5VA

    Measuring AccuracyVoltage0.2%
    Current0.2%
    Active Power0.5%
    Reactive Power1.0%
    kWh0.5%
    kVarh1.0%
    Frequency±0.05Hz
    Harmonic±1%
    Power SupplyVoltage Range 85-265V AC/DC; 24V or 48V DC (±20%)
    Power Consumption

    ≤10VA

    Insulation resistance

    ≥ 100MΩ

    Power frequency withstand voltage

    Between Power supply//Switching Output// Current Input//voltage Input and Transmitting// Communication //Pulse Output//switching input AC 2 kV 1min;

    Between Power supply、switching output、Current Input、voltage Input AC 2 kV 1min;

    Between Transmitting、Communication、Pulse Output、switching input AC 1kV 1 min;


    3. Environment

    ConditionDescription&Value
    Temperature

    Operation: -25℃+65℃; Storage: -40°C ~+80°C

    Humidity

    ≤95%RH,no condensation,without corrosive gas

    Altitude

    ≤ 2500m


  • ShapePanelHousingCut out
    Unit: mmWidthHeightWidthHeightDepthWidthHeight
    48 Square49494444934545
    72 Square75
    756666986767
    96 Square96968686928888