ARTM-Pn Local Temperature Data Display Device
● Receive&Display Temperature Data: From up to 60 ATE Temperature Sensors
● Communication Methods: GFSK (with ATE Temperature Sensor)
● Communication Distance: 150m in open Area & 15m in Building
● Extra RS485 Communication: MODBUS-RTU
● DO/DI Function: 2 Over-temp Alarm Relay Outputs & 4 Digital Inputs
● Dimension: 96*82*96mm (L*W*H)
● Installation: Panel Mounted (Cut-out Dimension--92*92mm)
● Electric Parameter Meausurement: U,I,P,Q,F,kWh,kVarh (Optional)

PRODUCTS

  • Features

    1.jpg

    Real-time Temperature Monitoring Data Display


    ● Display Data of up to 60 ATE Series Temperature Sensors


    ● Paired with ATC450 built-in Transceiver


    ● Regionalized Temperature Data Display

    2.jpg


    DO/DI Function


    ● 2 DO (high temperature alarm& over temperature alarm)


    ● 4 DI (built-in 12V power source)

    3.jpg


    Keypads for Programming


    ●Temperature Monitoring Data Display


    ● Parameter Setting


    ● Temperature Sensors Binding Adjustment


    ● Alarm Display

    4.jpg


    Optional Electric Parameters Measuring Function


    ● U (Voltage)


    ● I (Current)


    ● P (Power)


    ● Q (Reactive power)


    ● F (Frequency)


    ● kWh (phase positive Kilowatt-hours)


    ● kVarh (Kilovar-hours)

    5.jpg


    Display Sample

    6.jpg


    Installation Instruction

    7.jpg


    Typical Connection

    8.jpg


  • Functions
    ARTM-PnARTM-Pn
    SensorATE100, ATE200, ATE300B, ATE300, ATE400
    Temperature precision±2℃
    Sensor number60
    Auxiliary Power SupplyARTM-Pn
    Auxiliary power upplyAC 85~265V,DC 100~300V
    Power consumption8W
    CommunicationARTM-Pn
    ProtocolModbus-RTU
    Rear portRS485
    Baud rate(bps)2400,4800,9600,19200
    Environmental requirementARTM-Pn
    Operating temperature-10℃~55℃
    Relative humidity≤95%
    Atmospheric pressure86kPa~106kPa
    Average work time without stoppage≥50000 hour