ASL100-Sx/16 series of switch driver (hereinafter referred to as driver) is Acre-bus output control module. The product meets the rules of Q31/0114000129C032-2017 ASL100 Intelligent Lighting Control System. European KNX communication bus is adopted to achieve intelligent lighting control of large buildings and public buildings. The latest single-chip microcomputer technology is adopted by the module. Thus, the module is an intelligent control module with high stability and reliability, such as smart panel and dry node that achieving intelligence of lighting control. The driver controls the on and off of high voltage circuit by the communication bus. 30V DC voltage is used for module power supply at the communication end and is used for system communication. The relay controls the mains on and off by the relay at the output end. The module is applicable to the resistance, inductance and capacity load.
2. Specification and model
3. Technical parameters
Power supply feature
KNX bus feeder
DC21…30V
Power supply current
<12mA
Power consumption
<360mW
Load current
<16A
External connection
KNX-TP1
Use twisted-pair cable conforming to KNX standard
Wiring terminal at load end
Terminating with 0.5nm~0.6nm torque
Operation and display interface
Programming key and relevant indicator
LED indicator is in red when waiting for programming and is in green during and after programming.