In the operation of the current transformer (CT) in the secondary loop must not be allowed to open, once the open, or a winding through the abnormal current (such as lightning current and harmonic current, capacitance charging current, inductance starting current, etc.), will have thousands to tens of thousands of volts open overvoltage, CT and secondary equipment damage, also a serious threat to personal safety, caused great economic losses. The use of current transformer secondary overvoltage protector (CTB) can effectively prevent accidents caused by abnormal high voltage on the secondary side of current transformer.
type
application
ACTB-3
1 circuit three phase or 3 circuits single phase
ACTB-6
2 circuits three phase or 6 circuits single phase
ACTB manufactured by our company is mainly used for abnormal overvoltage protection of the secondary side of CT, and the secondary side of the sensor is approximately short in normal operation. In circuit state, the output voltage is very low. Once abnormal peak overvoltage occurs in CT secondary open circuit, it can immediately respond to voltage limit and delay short circuit, thus playing a complete protection role. The panel shows the fault part, and whether there is source signal output. When the fault is eliminated, the circuit returns to its normal state and works normally again.
parameter
index
Normal leakage current
<20uA
Input resistance
>100MΩ
break-over voltage
AC 150V(±10%)(Default, can be set according to user requirements)
break-over time
50ms≤Ts≤250ms
operating life
1×105times
Relay contact capacity
Communication relay contact capacity
AC220/5A;DC110V/5A
Protective relay contact capacity
AC220V/15A
CT specifications
5A
Protection current
The secondary side peak over 150V
working environment
temperature
-20℃~70℃
humidity
≤95%RH
altitude
≤2500 米
reset mode
Press the "Reset" button or automatically reset while power off